For safety, observe all of the following conditions for DC power connections.
Table 3-3 DC power safety conditions
All power connection wiring should conform to the rules and regulations in the National Electrical Code
(NEC), as well as any local codes.
Each DC-input power supply connection is rated at 60A maximum. A dedicated, commensurately-rated DC
power source is required for each power entry module connection.
For DC power cables, Riverstone recommends that you use commensurately rated, high-strand-count
copper wire cable. Connection to the DC-input power supply requires one earth ground cable for the power
supply and two cable leads (a DC source and a DC return) for each power supply. The length of the cables
depends on your RS 32000 location. These cables are not available from Riverstone. They are available
from any commercial cable vendor.
DC power cables must be terminated by cable lugs at the power supply end. The lugs should be able to fit
over 1/4-20 terminal studs.
The source of power for the DC power supplies must be a reliably grounded SELV source.
Branch circuit overcurrent protection must be rated a maximum of 60A.
A readily accessible disconnect device that is suitably approved and rated should be incorporated in the
field wiring.
Table 3-4 DC power supply environmental specifications
Specification Measurement
Operating Temperature +5° to +40°C (41° to 104°F)
Non-operating Temperature -30° to +73°C (-22° to 164°F)
Operating Humidity 15% to 90% (non-condensing)